What is the difference between eccentric and concentric reducers

Jul 03, 2025

‌Structural design differences‌
‌Concentric reducer‌
‌Centerline alignment‌: The centers of the two ends of the pipe are on the same vertical axis (projected as a small circle inscribed in a large circle);
‌Symmetrical transition‌: The conical wall thickness changes evenly, suitable for vertical or symmetrical pipe systems‌.
‌Eccentric reducer‌
‌Centerline offset‌: The centers of the two ends are not on the same straight line (projected as a small circle circumscribed in a large circle);
‌Single-sided straight design‌: One side is a straight side (top or bottom of the pipe), and the other side is inclined‌.

 

Installation method comparison

Installation Scenario‌ ‌Concentric reducer‌ ‌Eccentric reducer‌
Horizontal pipe‌ Not applicable (prone to fluid accumulation) ‌Required‌:
• Liquid pipes: straight side down (to prevent sedimentation) ‌
• Steam/gas pipes: straight side up (to prevent condensate accumulation) ‌
‌Vertical pipe‌ Applicable (centrally symmetrical and without risk of fluid accumulation) Not applicable
‌Water pump interface‌ For water outlet only‌ ‌Suction port must be selected:
• Install with the straight edge facing upward to avoid bubble accumulation and cavitation

Eccentric Reducer

Core application scenarios‌
1. Applicable scenarios for concentric reducers‌
‌Vertical pipe system‌: building water supply riser, chemical tower connecting pipe‌; ‌Scenarios without gravity flow requirements‌: air conditioning air supply pipe, compressed air pipe‌.

2. ‌Scenario for rigid demand of eccentric reducer‌
‌Water suction pipe before pump: prevent bubbles from gathering and damaging impeller (fire/chemical pump room); ‌Gravity flow drainage pipe: maintain slope when laying horizontally to avoid sewage sedimentation and blockage (municipal drainage pipe); ‌Space-constrained pipeline: straight edge fits the structure when installed against beams/walls to save space (dense pipe gallery). ‌️‌

 

Consequences of wrong selection‌
‌Concentric pipe is used for pump inlet by mistake; air pockets accumulate on the top → cause cavitation of water pump → damage to impeller; ‌Eccentric pipe is installed in reverse direction; straight edge of liquid pipe faces upward: solid sedimentation and blockage; straight edge of steam pipe faces downward: condensate backflow causes water hammer

Concentric Reducer